Cummins Generator QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) Does Not Transfer
What this problem usually means
The generator runs but the house load does not transfer, or the load does not transfer back to utility. Two branches cover this: the transfer switch failed to transfer to utility with no fault code, and Code 79, failure to transfer to the generator set.
Likely causes
- Transfer switch faulty
- Utility switch-position wire disconnected or broken
- Generator set main AC circuit breaker off
- Faulty positional switch or transfer switch component
How to fix it — step by step
- Warning: do not open the transfer switch and do not try to move it manually. Utility and generator sources meet in that enclosure, and mishandling can backfeed power onto utility lines.
- For failure to transfer to the generator: verify the main AC circuit breaker on the generator set is On. A breaker found off is the fix. For failure to transfer back to utility, note whether utility power has actually been restored and stable.
- If the breaker is On and the switch still does not transfer in either direction, the pinpoint is the transfer switch, its positional switch or the switch-position wiring.
- Have the utility switch-position wire, wire connections and transfer switch checked by an authorized electrician or Cummins dealer. Report which direction failed to transfer.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the fault is internal - there is no documented owner fix beyond the steps above. If you're not comfortable taking it apart yourself, a repair shop is the next step.
Parts that commonly fix it
No specific replacement part is documented for this fault. If the checks above do not clear it, your generator likely needs to be disassembled and an internal part replaced - and since the manufacturer publishes no procedure for that, it is the point where most owners hand it to a repair shop.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Cummins Generator QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) problems
- Won't Start
- Won't Turn On
- Code 12 - Overvoltage
- Code 13 - Undervoltage
- Code 14 - Overfrequency
- Code 15 - Underfrequency
- Code 2 - Low Oil Pressure
- Code 29 - High Battery Voltage
- Code 32 - Low Cranking Speed Sense
- Code 35 - Control Card Failure
- Code 36 - Stopped Without Fault Condition
- Code 4 - Overcrank
See all Cummins QuietConnect RS13A / RS17A / RS20A / RS20AC (GSBB/GSBC) codes & guides →