Bradford White Water heater ICON System (SIT, atmospheric & direct vent) 4 flashes
What it should look like on your machine
then it repeats
4 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
High tank temperature: the SIT ICON control shut down because tank temperature exceeded the setpoint.
Likely causes
- Tank temperature genuinely above setpoint - control operation fault
- Heat migration from the plumbing system heating the tank
- Failed gas valve control
How to fix it — step by step
- Check whether tank temperature exceeds the setpoint with a thermometer at a nearby hot faucet: water genuinely far above the setpoint means the control is overheating the tank; water at setpoint with the code present means the control is misreading or the heat is arriving from elsewhere.
- Check the operation of the control through a heating cycle: the burner should cut off as the tank reaches setpoint — a burner that runs past it condemns the control's temperature sensing.
- Verify there is no heat migration in the plumbing system pushing hot water back into the tank (a recirculation loop without a check valve, or a boiler loop tied in) — that cause is corrected in the plumbing, not with a part.
- Replace the gas valve if the control is overheating the tank: Replace the gas valve (the ICON control at the front of the tank): knob to OFF, main gas supply OFF, tank drained, the pilot tube, thermopile and igniter connections disconnected at the control, the control unthreaded from the tank fitting by turning it with a pipe section threaded into its inlet — never a wrench on the control body. Fit the new control with approved pipe joint compound on the tank fitting, reconnect everything, turn the gas on and leak-test the connections, fill the tank completely before relighting, and relight per the label. → Shop the gas valve at Amazon
- Prove two full heating cycles that stop at setpoint with no 4-flash code.
- If you hand it over, tell the technician: 4 flashes — high tank temperature — and the actual water temperature you measured against the setpoint.
- Verify after the repair: restore gas, water and power, then open a hot tap and let the heater fire and run for several minutes - the heater should run clean through the whole draw. If it comes back, the repair did not cure it: hand over the point in the sequence where it reappears, because that timing is the diagnosis
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Gas valve.
Parts that commonly fix it
- Gas valve$115–$500Shop at Amazon
- Tools for this job, if you need them$10–$65
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.