American Standard Heat pump 4A6H7024A1000C split system heat pump EEV board 9 flashes

What it should look like on your machine

then it repeats

9 flashes - then the pattern repeats. Count along with your machine and compare.

What this problem usually means

Read on the red Fault LED of the Electronic Expansion Valve control board in this American Standard heat pump, Table 6 in the Service Facts. Nine flashes means low superheat in cooling mode, which the manual attributes to an indoor TXV stuck open or an indoor fan failure. The same table notes faults 6 through 9 are stored in non-volatile memory. It matters because low superheat means liquid refrigerant is getting too close to the compressor, risking floodback damage, and the manual directs diagnosis at the indoor expansion device and indoor airflow rather than at the outdoor EEV itself, since in cooling the outdoor EEV drives fully open.

Likely causes

  1. Indoor TXV stuck open
  2. Indoor fan (blower) failure or severely reduced indoor airflow
  3. Dirty indoor air filter restricting airflow over the evaporator
  4. Suction temperature sensor out of calibration, reporting false superheat

How to fix it — step by step

  1. Record the code before cycling power: count nine flashes on the EEV board and note the fault is stored in memory; check the indoor air filter before anything else. Power-cycling can clear, change or recount the fault, so note the display, operating mode and outdoor temperature first.
  2. Safety: turn the system off, open the outdoor disconnect and breaker, verify with a meter that the unit is dead before touching wiring, and stay clear of the run capacitor terminals - a capacitor can hold a shock charge with power off.
  3. Locate the part: inspect indoor blower operation on a cooling call - the manual names indoor fan failure directly - and confirm air is moving at the registers
  4. Test: verify the suction temperature sensor is clipped tight to the suction line and insulated, and compare its resistance with Table 1 in the Service Facts; the manual's troubleshooting also asks that the outdoor unit be free of ice and debris with adequate clearance
  5. End point: replace a clogged filter and restore blower operation if the fan or its run capacitor tests bad. A stuck-open indoor TXV is sealed-system pro work, and stored EEV faults are cleared by the manual's Close-Test jumper procedure after the cause is fixed. Any work that opens the sealed refrigerant circuit, adjusts charge, or replaces a refrigerant pressure device is EPA-certified technician work only.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

Parts run $5–$80

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.

Related American Standard Heat pump 4A6H7024A1000C split system heat pump problems

See all American Standard 4A6H7024A1000C split system heat pump codes & guides →