York Heat pump YHJ(D,F) / YHJR series X/L on (steady, at thermostat)

What this problem usually means

Table 3 of Johnson Controls manual 835961-UIM-B-0412 lists the X/L output held On as 'Incorrect Defrost Curve - jumper selection'. The demand defrost control chooses its defrost initiate curve from a selection jumper, and the manual is explicit about a wrong one: jumper position 4 is not used and the control will not allow the compressor to operate there, it will not energize the compressor if the jumper is in a position not described for the model or is missing, and it displays the proper fault code when a defrost curve jumper error is present. The control reads the jumper only when the Y and W inputs are de-energized, so the correction must be made with thermostat calls off or power cycled.

Likely causes

  1. Defrost curve jumper missing
  2. Jumper in position 4 or another position not valid for the model
  3. Jumper disturbed during service and replaced incorrectly
  4. Replacement control installed without setting the curve for the model

How to fix it — step by step

  1. Record the steady X/L indication before changing the jumper, and photograph the jumper's as-found position for comparison with the manual's curve table for the exact model.
  2. Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
  3. Remove the outdoor control-box panel and locate the defrost curve selection jumper on the defrost control, shown in the manual's defrost control figure.
  4. Set the thermostat to OFF so the Y and W inputs are de-energized (the manual states the control only reads the jumper in that state), place the jumper on the numbered position the manual's Table 4 assigns to this model, and restore power.
  5. Force a defrost with the TEST input and confirm the X/L output flashes the active curve number, the compressor operates, and the steady X/L error is gone.

Did that fix it?

Worked through the steps? Say where you landed - it pinpoints what to do next.

Parts that commonly fix it

What fixed yours?

Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.

Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.

Manual & model number

Find your model number on the outdoor unit's rating plate. It's the key to the right manual pages and the right parts.