York Heat pump YHJ(D,F) / YHJR series X/L 2 flashes (at thermostat)
What it should look like on your machine
then it repeats
2 flashes - then the pattern repeats. Count along with your machine and compare.
What this problem usually means
In Johnson Controls installation manual 835961-UIM-B-0412 for the York YHJ(D,F)/YHJR split heat pumps, Table 3 (X/L Output Categories) gives two flashes on the X/L output as 'Pressure Switch lockout - last mode of operation was heating'. The X/L terminal connects the outdoor control to the room thermostat, which flashes the code where the homeowner can see it, with a three-second delay between flashes. The pressure switch section explains the lockout: a switch opening stops the compressor, and a second opening inside the six-hour accumulated run-time timer causes a soft lockout, during which the control de-energizes the compressor and energizes X/L with this code. It resets when the thermostat call is interrupted or the TEST terminals are shorted over two seconds, after the fault is corrected.
Likely causes
- Refrigerant pressure switch tripping on low charge (loss of charge)
- High pressure from airflow failure in heating (dirty filter or indoor coil)
- Pressure switch failing or its circuit intermittent
- Refrigerant restriction causing repeated trips
How to fix it — step by step
- Record the two-flash X/L code at the thermostat before interrupting the call, because interrupting it is also the reset and erases the display.
- Safety first: Turn the outdoor disconnect off and switch the breaker off, then verify the unit is dead with a meter before touching wiring; treat the run capacitor as charged and discharge it safely, because it can hold a charge after power is removed.
- Replace a clogged indoor filter and check both coils, then remove the outdoor control-box panel to inspect the defrost control and the pressure switch, loss-of-charge and over-temperature switch connections the manual shows wired to it.
- A technician should connect gauges and determine which switch and pressure direction is tripping: low suction points to charge or restriction, high discharge in heating points to indoor airflow; normal pressures at trip condemn the switch or its wiring.
- Fix the proven cause, then reset the soft lockout by interrupting the thermostat call or shorting the TEST terminals for more than two seconds, as the manual directs. Any refrigerant-side repair, charge adjustment or sealed-system work is EPA-certified-technician work only; do not open the refrigerant circuit yourself.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Air filter.
Parts that commonly fix it
- Air filter$5–$30Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.