Generac Generator Guardian Air-Cooled with Evolution Controller Overload Remove Load 2100
What this problem usually means
Electrical load demand exceeds the generator rated capacity, codes 2100 through 2103, with a red light. The generator protects itself by shutting down. The fix is load reduction, proven by a clean run at the reduced load.
Likely causes
- Total simultaneous load above the generator rated capacity
- Several large appliances starting at once, stacking their startup surges
- Load management device not functioning or lockouts not configured
How to fix it — step by step
- List what was running when the shutdown happened, and mark which loads are not critical in an outage, such as extra air conditioning, electric heating, pumps and large appliances beyond the essentials like a sump pump and refrigerator.
- Remove the non-essential loads: unplug them or switch off their breakers in the main panel, so the remaining simultaneous load sits below rated capacity.
- Turn the generator main line circuit breaker to OFF, then clear the alarm: press OFF, then press ENTER. Never start the generator while it is under load.
- Restart and return to AUTO. Let the engine warm up for one to two minutes, then turn the main line circuit breaker to ON and restore the utility breaker to ON so the unit can recognise restored utility power.
- Check any load manager is functioning and its lockouts are configured, so large loads are staggered instead of starting together.
- If the same code returns at the reduced load, remove more load and repeat once. A unit that still overloads at a clearly reduced load needs dealer diagnosis. Report the load list you tested with.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
Then the fault is internal - there is no documented owner fix beyond the steps above. If you're not comfortable taking it apart yourself, a repair shop is the next step.
Parts that commonly fix it
This fault usually does not need a replacement part - the fix is in the steps above. If your generator does need a part, start with the link above.
What fixed yours?
Fixed this on your machine? Tap what did it - reports from owners set the percentages on this page.
Source: manufacturer / repair documentation. Codes can vary by model — confirm against your manual.
Manual & model number
Find your model number on the unit's rating plate. It's the key to the right manual pages and the right parts.
Related Generac Generator Guardian Air-Cooled with Evolution Controller problems
- Overspeed 1200
- Overvoltage 1800
- RPM Sensor Loss 1500
- Runs Rough
- Starts Then Stops
- Underspeed 1600
- Undervoltage 1900
- Auxiliary Shutdown 2800
- Controller Fault
- High Temperature 1400
- Low Oil Pressure 1300
- Overcrank 1100
See all Generac Guardian Air-Cooled with Evolution Controller codes & guides →