Generator won't start

A generator that will not start is almost always failing on one of four supplies: battery power to crank it, fuel, oil, or air and spark. The order below works through them the way the machines report them, and it splits early, because a standby unit that should have started on its own during an outage and a portable that will not pull to life fail for overlapping but not identical reasons. If the power is out right now, start with safety, then read the machine before you touch it: most standby controllers store a fault code that names the failed branch outright, and clearing it before you note it throws the diagnosis away.

First checks: these apply to every brand

  1. Safety first, every time — Generator exhaust carries carbon monoxide, an odourless gas that kills people in outages every year. A portable runs outside only, never indoors and never in a garage even with the door open, set well away from the house with the exhaust pointing away from windows and doors, and it cools before refuelling. A standby unit is safer to check but it is wired into your gas supply and your electrical panel: read its display, check its battery and oil, and stop there. Never open a transfer switch, never work on the gas train, and never connect a portable to house wiring without a transfer switch, because backfeeding power onto the street wiring can kill a line worker who reasonably believes the line is dead.
  2. Read the controller or the panel before anything else — On a standby generator, look at the controller display or status lights first. A stored fault code or alarm, such as low oil pressure, overcrank, RPM sense loss or a charger fault, is the machine naming the branch that failed, and the brand pages below decode each code to its checks and parts. Note the exact code before you clear or reset anything. On a portable, the equivalents are the indicator lights: a low oil light, an overload light, or a carbon monoxide shutdown light that is still flashing is the machine telling you which protection stopped it, and each one has a different fix.
  3. Check the battery: the standby unit's most common failure — A standby generator lives or dies by a battery that is only ever asked to work during an outage and its weekly exercise. A battery that has aged out, has corroded or loose terminals, or has been let down by a failed battery charger produces the classic symptoms: a click and no crank, slow cranking, a low battery or charger alarm on the controller, or a unit that quietly failed its exercise runs for weeks before the outage arrived. Check that the terminals are clean and tight, and treat a battery much past three or four years old as the prime suspect. The same applies to an electric start portable that cranks weakly or not at all while starting fine on the recoil starter: the split between electric and recoil starting isolates the battery circuit, and on many portables the battery switch simply being off is the whole fault.
  4. Confirm the fuel, and that it is fresh — On a portable, work the simple chain in order: fuel in the tank, the fuel valve open, and the choke set for a cold start. Fuel that has sat in the tank or the carburettor over a season is the single most common reason a portable that ran last year will not start this year; if the fuel is old, drain it and start again with fresh fuel rather than cranking stale fuel through the carburettor. On a dual fuel portable, confirm the selector matches the fuel actually connected and the LPG cylinder has gas and its valve is open. On a standby unit, confirm the gas supply: the shutoff valves on the line to the unit open, and on propane, gas in the tank. A standby that cranks strongly but never fires is starved of fuel or spark, and the gas train past the shutoff valve is a technician's job.
  5. Check the oil before you crank again — Generators protect themselves with a low oil shutdown, and it stops far more starts than any broken part. Pull the dipstick: oil below the low mark, or a unit sitting on a slope so the oil pools away from the sensor, will crank and refuse to fire, or start and stop again within seconds. Top up to the full mark with the oil type the filler cap calls for, set a portable on flat, level ground, and retest. If the oil level is correct and the machine still reports low oil pressure or stops as if it were low, the fault is the pressure switch or the oil system itself, which is where owner checks end.
  6. Air filter and spark plug: the portable classics — An engine needs air and a spark as surely as fuel. The air filter sits behind a cover that usually opens with clips or a single screw: a filter clogged with dust or soaked with oil starves the engine and produces rough running, black smoke or a start that dies as the choke comes off. The spark plug is the other half: remove it with a plug socket and read it. A plug that is fuel fouled and wet points back at flooding or choke; a dry, tan plug with a worn or bridged gap points at the plug itself; no spark at all when the plug is grounded against the engine and cranked points at the ignition, and that is service work. A fresh plug and a clean filter fix a large share of portable no starts outright.
  7. Respect the overcrank lockout — Standby controllers limit how long and how often the engine may crank, then lock out on an overcrank fault to protect the starter. If your unit shows overcrank, it has already tried repeatedly and failed: the cause is one of the branches above, most often fuel or battery, and resetting the controller and letting it crank again without fixing the branch just runs the battery down and overheats the starter. Note the code, work the battery, fuel and oil checks, and only then clear the fault and retest once. A unit that still will not fire after those branches are proven belongs to a generator technician.
  8. If it starts but the house stays dark, the fault moved — Starting is only half the job. A standby unit that runs while the house stays dark has failed at the transfer: the transfer switch has not moved the house onto generator power, which is switch and sensing work for a technician, not an owner adjustment. A portable that runs with nothing powering up is simpler: check the output breaker or overload reset on the panel, confirm each plug is fully engaged (the twist-lock outlet needs its quarter turn), and reduce the load, because an overload at startup trips the output before anything runs. The brand pages below carry each model's transfer and output faults in detail.
  9. Starts then dies: use the timing and the panel lights to split the branch — If the engine does start, this is a different fault from a no-start, and how long it runs before it stops is the main discriminator. Dying within seconds, often as the choke comes off or just after firing, points first at a protective shutdown — low oil, or on a standby unit a stored fault such as overspeed. Dying after a few minutes of apparently normal running points at fuel starvation that builds over time: a tank vent that is not letting air in, a fuel valve or strainer that passes a trickle but not a flow, or a carburettor that can fill a float bowl slowly but not keep up. Dying only when a load is connected points at overload or at an engine that cannot carry load. Before you restart it, read the panel again exactly as in check 2: on Generac portables a COsense shutdown shows a blinking red light for accumulating carbon monoxide and a blinking yellow light for a COsense system fault, and Champion's CO Shield uses the same red-for-CO, yellow-for-fault pattern — a CO shutdown is not a fault to clear and retry in the same spot, it is the machine telling you to move it to open air outside, exhaust pointing away, before any other check. Note the run time, whether a load was connected, and any light or code, then work the next checks in order.
  10. Starts then dies, seconds in: the low-oil shutdown doing its job — or lying — The low-oil protection that blocks a start in check 5 also stops a running engine, and in this branch it is the first suspect when the machine dies within seconds. Honda's Oil Alert, fitted across its range, is designed to stop the engine before the oil level in the crankcase falls below a safe limit, and Honda states the same system can operate on a slope, because the oil pools away from where it is sensed; Champion and Generac troubleshooting tables give the identical pair for 'generator shuts down during operation' and 'engine starts and shuts off right away': low oil level, fill the crankcase to the proper level, place the generator on a flat, level surface. So retest properly, not from memory: engine off, machine on flat, level ground, dipstick wiped, reinserted and read as your manual directs (Honda's procedure is to insert and remove it without screwing it in), and top up to the upper or full mark with the oil the filler cap calls for. A machine that then runs was genuinely low or genuinely tilted, and the sensor has done its job. If the level reads correct on level ground and the machine still dies in seconds with a low-oil light or a low-oil-pressure fault, the level is proven and the suspicion moves to the sensing side — the low-oil sensor or, on a standby unit, the oil pressure switch and oil system, which check 5 already marks as the end of owner checks. One test is carried here by name only and is NOT instructed on this page: disconnecting (unplugging) the low-oil sensor wire to see whether the engine then stays running. No manufacturer manual or official support page read for this guide documents that test for owners, so it is not presented as a step; a service dealer who performs it can condemn the sensor, and a sensor proven faulty that way is replaced, never left disconnected, because running with the protection defeated removes the shutdown that saves the engine when the oil really is low.
  11. Dies after a few minutes: fuel starvation that builds — cap vent first, then the fuel valve — An engine that runs normally for minutes and then fades and stops is usually being starved slowly, and the timing itself is the test result. As fuel leaves a sealed tank, air must enter to replace it; Honda's EU2200i manual lists the fuel filler cap vent lever being in the OFF position as a cause in its troubleshooting, and on models with a vented cap or a vent lever, a closed or blocked vent lets a vacuum build in the tank until fuel flow slows to nothing — which takes minutes, matching the symptom. The discriminator is free: the next time it dies, loosen the fuel cap. A hiss of air rushing in, and an engine that restarts at once and runs again, proves the vent path; refit the cap and, if it dies again on the same timing, the cap vent is the fault and the fuel cap is replaced. If loosening the cap changes nothing, move one step down the same path: confirm the fuel valve is fully open (a partly open valve, or the dirty fuel valve Champion lists under rough running and hunting, passes enough fuel to start and idle but not to run), and on models with a fuel valve filter or a tank strainer, treat a restricted strainer as the same starvation in a different place — Honda's table puts a restricted fuel strainer in the dealer-level remainder for exactly this reason, so cleaning a strainer your manual shows as owner-serviceable is in scope, and opening the fuel system beyond that is not.
  12. Starts, runs briefly, then dies — and the fuel is old: stale fuel and the carburettor — If the cap vent and valve are proven and it still dies, judge the fuel itself and then the carburettor it has been sitting in. Honda's correction for bad fuel — a generator stored without treating or draining the gasoline, or refuelled with bad gasoline — is to drain the fuel tank and the carburettor and refuel with fresh gasoline, and Generac's table gives stale fuel the same treatment: drain the tank and fill with fresh fuel. The pattern that condemns this branch rather than the vent is a machine that will run on choke, or run briefly and die as the choke comes off, because a partly blocked carburettor can pass the rich mixture a choked engine needs but not the leaner mixture it runs on; Champion's troubleshooting names the matching internal causes directly, a dirty fuel valve to clean and a carburettor that is dirty and running lean. So: drain and replace suspect fuel first and retest on fresh fuel before any part is condemned, because fresh fuel alone clears a share of these. If it still dies the same way on fresh fuel with the vent and valve proven, the carburettor itself is the pinpoint — cleaning or rebuilding it is the fix, and on a standby unit, or if you are not set up to drain fuel safely into an approved container away from ignition sources, that is service work. Never drain or refuel a hot engine: let it cool first, as check 1 requires.
  13. Choke left on: the start that dies as it warms up — A choke is a starting aid, not a running setting, and a machine that starts readily, runs for a short while and then dies rich — rough, smoky, or with a plug that comes out wet and blackened as in check 6 — may simply never have been taken off choke. Generac lists over-choking among its start-and-run-rough causes with the correction to set the choke to the no-choke position, and Champion's tables list the choke lever in the wrong position under both rough running and failure to supply power, with the correction to move the control to RUN. The test costs nothing and separates this from the carburettor branch above: restart from cold with full choke as your manual directs, then move the choke fully to RUN (or the EZ Start dial to the RUN position) as soon as the engine fires and smooths, and let it run. An engine that now keeps running was choked, not blocked. An engine that will only keep running with the choke partly on has given you the opposite result, and it is a useful one: it needs the extra fuel the choke provides, which points back to the starvation and dirty-carburettor checks above rather than at the choke itself. On models with automatic choke and throttle control there is no lever to leave on; a warm engine that still behaves choked on one of those is an engine control fault, and that is dealer work.
  14. Dies only when the load comes on: overload, tested by subtraction — If it idles and runs unloaded indefinitely but dies, trips or shuts down when appliances are connected, stop working the engine branches: the load is the variable, so test by removing it. Champion lists a generator that is overloaded under both 'cannot supply enough power or overheating' and repeated circuit breaker tripping, and Generac's table for an engine that runs well at no load but bogs when load is applied separates a short circuit in a connected load from a generator that is simply overloaded. Unplug everything, restart with nothing connected, and confirm it runs steadily; then add one known-good load at a time, starting with the smallest, and leave motor loads — fridges, pumps, air conditioners, power tools — until last, because their starting surge is several times their running draw and two of them starting together is the classic trip. The load at which it dies, or the single appliance that kills it every time while others run, is the answer: either the total exceeds what the machine can supply, in which case the fix is load management and not a part, or that one appliance or its cord is faulty or shorted, in which case it is the appliance that is condemned. A machine that dies under a modest single load it should easily carry has failed this test in the other direction, and the remaining suspects are the fuel and carburettor branches above and the spark arrestor below.
  15. Runs progressively worse, lacks power, then dies: clean the spark arrestor screen — The spark arrestor is a fine screen in the muffler outlet that stops sparks leaving the exhaust, and it slowly carbons up until it chokes the exhaust itself. Generac lists a clogged spark arrestor under both an engine that lacks power and one that bogs under load, with the correction to clean the spark arrestor screen, and Champion lists a clogged spark arrestor under engine shuts down during operation and under starts but runs roughly, with the same correction. The symptom pattern that points here rather than at fuel is gradual: a machine that has lost power over a season, hunts or falters, and now dies, rather than one that stopped suddenly. The service is owner work in the manuals and the location is consistent: let the engine cool completely first — the muffler stays hot long after shutdown — then remove the screws holding the cover plate that retains the spark arrestor to the muffler, take the screen out, and remove the carbon deposits carefully with a wire brush. A screen that is damaged, holed or still blocked after brushing is replaced rather than cleaned, and Champion's caution is explicit that failure to clean the spark arrestor results in poor engine performance, so a cleaned screen that restores full power has proven the diagnosis. Refit the screen and cover before running: the arrestor is a fire-safety part, not an optional extra, and the machine is not run without it.
  16. Dies with a speed fault, or races and shuts down: overspeed, low speed and the governor — A generator makes the right voltage only at the right engine speed, so a shutdown that comes with a speed code is the controller protecting the machine and everything plugged into it. On a standby Generac, an OVERSPEED alarm (codes 1200-1207) means the controller detected high RPM; Generac lists among its causes a lean fuel condition or a sudden change in load, a faulty RPM sensor or signal loss, governor failure, a sticking throttle or mechanical binding, and incorrect fuel type or pressure for the configuration — and its owner-level response is deliberately narrow: verify the fuel shutoff is open, the fuel selection matches the fuel actually supplied, the air filter is not blocked, remove all loads, clear the alarm once and attempt one restart, and if it recurs, stop and use an authorised service dealer, because governor, throttle and fuel-pressure work is theirs. Honda builds the same protection into its portables in plain form: an overspeed detection function that automatically stops the engine if the speed becomes abnormal, and an abnormal voltage detection function that stops it during generation — so a Honda that dies with no fuel, oil or choke explanation has often shut itself down on speed or voltage, and Honda's instruction after checking the oil level and waiting a few minutes is one restart attempt, then the dealer. At the other end of the scale, a governed engine running too slowly is also a shutdown and output problem rather than a setting to chase: a manufacturer repair manual for capacitor-excited portables states the generator is designed to produce no output if engine speed falls about ten percent or more below the required speed, and Champion's verdict on a defective engine governor and on an engine that gallops is the same in both its manuals — contact the service line. Do not adjust a governor yourself to cure a shutdown: the manuals treat governor tampering as damage-causing, and a speed fault that survives the fuel, air and load checks above is a pinpoint, not an adjustment.
  17. Runs but no power: start at the panel — breaker, GFCI and circuit protector before any part — When the engine runs normally and the outlets are dead, work the panel in order before suspecting the generating side, because the commonest causes are protections doing their job. Every manufacturer table read for this guide puts the same three first. Generac: circuit breaker OPEN — reset it; GFCI receptacle OPEN, if equipped — correct the ground fault and press the reset button on the GFCI; and before either, rule out the load side, because its other two listed causes are a poor connection or defective cord set and a connected device that is simply bad. Honda's 'no power at the AC receptacles' table is the same list in its own terms: the AC circuit breaker left in the OFF position after starting — switch it ON; the GFCI system activated — test the GFCI and press the GFCI RESET button; an AC circuit protector tripped — check the AC load and reset the protector; and a faulty power tool or appliance. So the test sequence is: unplug everything, plug one small known-good appliance directly into the generator with no extension cord, reset any tripped breaker or protector and press the GFCI reset, and retest. Power at that outlet means the generator is making electricity and the fault was the cord, the appliance or the protection that tripped; note that a GFCI can kill only its own receptacle while others stay live, so test more than one outlet before calling the whole machine dead. A breaker, protector or GFCI that trips again immediately, with nothing or only the known-good appliance connected, has stopped being a reset and become a diagnosis: there is a ground fault or short to find, and repeated resetting is not a fix. Keep check 1 in force throughout — this is live output on a running machine, never open the panel beyond the resets the manual describes, and a standby unit whose house side is dark is transfer switch work, as check 8 already states.
  18. Runs but no power, with the overload light on: overload and overheated inverter or internal circuit — On inverter portables and electronically protected models, an overload does not necessarily trip a breaker you can see: the machine cuts its output electronically and keeps the engine running, which presents exactly as a healthy engine and dead outlets. Honda's table separates this case by its lights: the OUTPUT indicator OFF and the OVERLOAD ALARM indicator ON means check the AC load, stop and restart the engine, and check the cooling air inlet; a second Honda cause in the same table is an internal circuit that has overheated, corrected by stopping the engine, reducing the electrical load, waiting a few minutes for the circuit to cool, and restarting. Champion's equivalent is a panel control rather than a light: an AC overload with the button illuminated red is corrected by reducing the AC load and pressing the overload reset button until it illuminates green. The discriminator against the breaker branch above is that nothing on the panel is mechanically tripped and output returns — or does not — on a stop, cool and restart with all loads removed. A machine that restarts into normal output with no load was overloaded or overheated, and the fix is the load, added back one item at a time as in the dies-under-load check. A machine that comes back with the overload indication lit and nothing connected at all has an internal fault rather than a load problem, and that is where owner checks on the electrical side end.
  19. No output on every outlet, nothing tripped: the automatic voltage regulator (AVR) — If the panel protections are all proven — breakers on, GFCI reset, protectors reset, a known-good appliance tried direct — the fault has moved inside the alternator end, and on an AVR-regulated machine the regulator is the first internal suspect. The AVR is the electronic module, usually mounted at the alternator end under its cover, that senses the output voltage and controls the field current that creates it; when it fails open, the engine runs at full governed speed and the outlets show nothing, or only a few residual volts. Champion's no-AC-output table names this part directly: faulty AVR (auto voltage regulator) — replace the AVR, and it assigns that replacement to a service center, as it does the brush assembly in the check below. Honda's regulated designs carry the same component under its own names — the iAVR in the EM range and the digital AVR in its wiring diagrams — and Honda's owner-level verdict for a machine whose panel causes are all eliminated is the same shape: faulty generator, take it to an authorised dealer or refer to the shop manual. The honest owner-level discriminators are therefore eliminative and observational rather than a bench test: output absent on every outlet and every circuit, not just one; nothing tripped; output that died suddenly, often during or just after a heavy load or an overload event, rather than fading over a season; and on models with an output meter or indicator, an engine running at normal speed with no output indication. Those together pinpoint the AVR as the prime suspect to hand to service — do not condemn it past that on this page, because the stator and rotor windings give the same dead-outlets symptom and separating regulator from windings is meter work inside the alternator end, which is service work around a running machine's electrics.
  20. Know which excitation design you have: capacitor-excited brushless vs AVR-regulated — Not every conventional generator has an AVR, and condemning one on a machine that never had one wastes the repair. Smaller and simpler brushless portables are commonly capacitor-excited instead: a capacitor in the alternator end, a cylindrical component with two terminals, forms part of the excitation circuit that builds the output voltage, and a failed capacitor gives the same headline symptom as a failed AVR — engine running normally, no output. The test for it is a manufacturer repair-manual procedure and it is done with the engine stopped, because the same manual warns that extremely high voltage is present at the capacitor terminals while the generator is in use. Discharge the capacitor before handling it even with the engine off — the manual's method is to place a conductor such as a screwdriver with an insulated handle across its terminals, touching only the insulated handle — then disconnect all wire leads from the terminals and test with an ohmmeter on its high resistance scale (the manual specifies R x 10k) or a capacitor checker: the meter should deflect momentarily toward zero and then climb slowly toward infinity as the capacitor charges, and reversing the leads should give the same result. A capacitor whose meter does not deflect toward zero, or deflects to zero and stays there, is open or shorted and must be replaced, like-for-like in capacitance and voltage rating. A capacitor that passes that test on a brushless machine with no output has cleared this branch, and the remaining causes are in the windings, which is service work. If your machine is AVR-regulated or an inverter model, this check does not apply to it — the AVR check above and the overload check before it are its branches.
  21. Brush-type machines with no output: worn brushes and dirty slip rings — One more design split decides whether this check exists for your machine at all. Brush-type (direct-excited) alternators carry their field current through a pair of carbon brushes riding on slip rings on the rotor, usually reached by removing the alternator end cover; brushless and inverter machines have no brushes to wear. Brushes are a wear item: as they shorten, contact with the slip rings weakens and output becomes intermittent, low, or stops altogether, often after long service rather than suddenly. Champion's no-output table lists the faulty brush assembly alongside the faulty AVR, with the same disposition: replace the brush assembly, service center. The owner-level evidence is again eliminative plus visual where your manual shows brush access as owner work: every panel protection proven, output absent or intermittent, and on inspection brushes that are worn short, cracked, sticking in their holders instead of moving freely against their springs, or slip rings that are darkened and scored rather than bright. Brushes and slip rings are judged as a pair, because new brushes on a rough or dirty ring wear out in hours. If your manual does not show brush access, do not go looking for them inside the alternator end — record the pinpoint, worn brush assembly suspected on a brush-type machine with all panel causes eliminated, and hand it to service with the AVR check's result, since the two parts sit in the same part of the machine and are separated by the same meter work.
  22. Output at or near zero after long storage: lost residual magnetism and flashing the field — The last no-output cause is the one that explains a machine that was fine when it was put away. A brush-type alternator starts generating from a small amount of residual magnetism left in the rotor after shutdown; if that magnetism is lost — which the Briggs & Stratton portable generator service manual states usually occurs if the unit is out of use for a long period of time — the output voltage remains at zero however well the engine runs. That manual gives the branch its discriminator and its named fix. First measure the output properly: an AC voltmeter in a receptacle, all loads disconnected, engine started, stabilised and warmed up; if zero volts or less than about 6 volts AC is indicated, the manual's next test is Test 2, flash the field, whereas low voltage above that threshold with normal frequency points elsewhere in its diagnostic sequence. Flashing the field means restoring the residual magnetism by briefly applying a DC battery to the brushes: in the manual's procedure for units equipped with a voltage regulator or a bridge rectifier, a 12-volt DC battery is connected by jumper leads with the engine at running speed, positive to the positive brush — identified as the brush closest to the rotor bearing — and negative to the negative brush, farthest from the bearing, for about five seconds, then disconnected and the AC output checked, with the engine shut down, restarted and checked again. This is included as a documented manufacturer service procedure, not a first resort: it applies only to brush-type machines, some units have field boost that flashes the field on every startup and should never lose residual magnetism unless the field boost itself has failed, and it is work at the brushes of a running alternator — if you are not confident identifying the brushes and their polarity from your model's manual or wiring diagram, the correct owner action is to hand service the pinpoint in those words: output under 6 volts AC, residual magnetism suspected, flash-the-field test requested. A machine that builds proper voltage after flashing and holds it on the restart was only ever magnetically flat; one that does not build voltage even during the flash has a deeper alternator fault, and the diagnosis moves to the windings, which is service work.

Generator won't start by brand

The checks above fix most cases. For the causes, codes and parts specific to yours, pick your brand:

Parts that commonly fix it

Parts run $5–$150

Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.

When to call a pro: Call a generator technician for anything inside the transfer switch, the gas train past the shutoff valve, the controller or sensing boards, and any standby unit that still will not start after the battery, fuel and oil branches are proven: the machine is wired into your fuel supply and your panel, and both sides of that are licensed work. Never run a portable generator indoors or in a garage, and never connect one to house wiring without a transfer switch.