Furnace limit switch keeps tripping
The high limit switch is a safety that shuts the burners off when the furnace gets too hot, then lets them relight once it cools. In most homes the switch is doing its job and the real fault is restricted airflow making the furnace overheat. Fix the airflow first, in the order below, and only blame the switch after airflow is proven good.
First checks: these apply to every brand
- Know which switch tripped and where it sits — The primary high limit is a small disc or probe switch mounted on the metal wall between the burners and the blower, above the heat exchanger, with its sensing end reaching toward the heat exchanger or the supply plenum. It resets automatically as it cools. Rollout switches are different parts. They sit on the burner box near the burners and have a small manual reset button. Auxiliary limits sit near the blower on some downflow and horizontal furnaces. A limit code on the control board LED, decoded by the sticker inside the door, tells you the limit circuit opened, but the airflow checks come before any part swap.
- Replace the air filter first — Cut power at the furnace switch, pull the filter from its slot or return grille, and hold it to a light. If you cannot see light through it, replace it with the same size. A clogged filter is by far the most common cause of limit trips, because too little air crosses the heat exchanger to carry the heat away. A very restrictive high MERV filter in a system not designed for it can cause the same trip. Restore power and run a full heat cycle. If the burners now stay lit until the thermostat is satisfied, the filter was the cause.
- Open closed registers and clear blocked returns — Open every supply register in the house, including in unused rooms. Closing registers raises duct pressure and cuts the total air moving through the furnace. Then clear return grilles of furniture, rugs, and boxes. A starved return has the same effect as a clogged filter. Retest with everything open. Trips that stop with all registers and returns clear were an airflow problem, not a bad switch.
- Check the blower wheel and blower speed — With power off and the blower door removed, look at the blower wheel, the squirrel cage in the blower compartment. Dust packed into its curved blades cuts the air it can move, even when the motor runs. A wheel you can see is caked needs cleaning, which is usually a pro job because the blower assembly comes out. A blower that runs slowly, hums, or starts weakly points to a weak motor or capacitor, which also starves airflow. If the wheel is clean and the blower runs at full speed, move to the switch test.
- Do not reset a rollout switch and walk away — If the tripped switch is a rollout switch with a manual reset button on the burner box, stop. A rollout trip means flame or heat escaped the burner area, which points to a blocked flue, a blocked heat exchanger, or a crack. Rheem's instruction for its furnaces is explicit: do not jumper or reset this switch and keep running the furnace. Pressing the reset once to confirm the trip is the limit of owner action. If it trips again, turn the furnace off and call a technician. The auto reset high limit needs no button. It resets on its own as the furnace cools.
- Test the switch with a multimeter, power off and cool — Let the furnace cool fully, cut power at the breaker, remove the access panel, and pull the two wires off the limit switch, noting which goes where. Set a multimeter to ohms or continuity. A healthy limit switch is normally closed, so a cool switch should read continuity, near 0 ohms. A reading of OL (open) on a cool switch means the switch has failed and needs replacement. A switch that reads continuity when cool is working at room temperature, so the trips are real overheating and the cause is airflow, gas pressure, or blower speed, not the switch. Never test with the furnace powered, and never judge a switch bad just because it reads open while hot. Opening when hot is its job.
- Replace with the exact rating if the switch failed — The opening temperature and reset differential are stamped on the switch body, for example a rating like 160-40, meaning it opens at 160 degrees F and resets 40 degrees lower. The replacement must match the original part number, opening temperature, probe length, and mounting for your furnace model. Never fit a switch with a higher rating to stop the tripping. That lets the heat exchanger run hotter than it was designed for and removes the protection. After replacing, run a full cycle and confirm the burners stay lit. If a new switch trips too, the airflow fault is still there.
Parts that commonly fix it
- air filter$5–$30Shop at Amazon
- limit switch$5–$35Shop at Amazon
- blower motor$95–$450Shop at Amazon
Typical ranges, checked Nov 2026. Your model’s exact part can land outside them.
When to call a pro: Call a pro if the limit keeps tripping after a new filter, open registers, and clear returns, if a rollout switch has tripped at all, or if the temperature rise is above the range on the furnace rating plate. Repeated overheating stresses the heat exchanger and a cracked heat exchanger can leak carbon monoxide into the house air. Never jumper or bypass a limit or rollout switch. If you smell gas, leave the house and call the gas utility or 911 from outside. If a CO alarm sounds, leave and call 911 from outside.