Navien Boiler NFB-H series E302 Error Code
What the E302 code means
E302 is low water pressure on the NFB-H fire tube boilers, and it requires a manual boiler reset. The built-in water pressure sensor has detected an insufficient water level in the boiler, and the factory installed pressure sensing low water cutoff has a minimum operating pressure of 6 psi by default. Unlike the NCB-H combi, which fills itself and reports E351, the NFB-H stops on E302 and waits for the system to be refilled and reset by hand.
Likely causes
- Low water pressure in the heating system
- Insufficient water level detected by the built-in water pressure sensor
- Water lost from the heating system, leak or discharged relief valve
- Make-up water supply closed or restricted
How to fix it — step by step
- Record the code before resetting: write down E302 exactly as shown on the NFB-H front panel, and record the system pressure shown with it.
- Safety: leave the boiler off while the system is low on water. Firing a boiler that is short of water can damage the fire tube heat exchanger, and the low water cutoff must never be bypassed to get heat.
- Locate the parts: the built-in pressure sensing low water cutoff and water pressure sensor are inside the NFB-H boiler, the make-up water feed and its shut-off valve are in the system piping at the boiler, and the system pressure is read on the front panel display.
- Test: check the make-up water supply is open and refill the system, watching the pressure rise. Pressure that rises and holds points to water lost earlier that still needs a source; pressure that will not rise points to the feed path, and pressure that falls again over hours to days proves a leak or a discharging relief valve in the system.
- End at the fix: refill the system above the 6 psi low water cutoff minimum to its normal cold fill pressure, find and repair any leak the pressure test proved, then reset the boiler manually from the front panel. If E302 returns on a full, leak free system, the pinpoint is the built-in pressure sensor or low water cutoff and a technician replaces it.
Did that fix it?
Worked through the steps? Say where you landed - it pinpoints what to do next.
Good - you're done. If it comes back, the causes at the top of this page are where to look first.
This fault usually needs a technician - but this is the part they would test first.
Then the likely broken part is the Water pressure sensor.
Shop the Water pressure sensor at Amazon
Also tied to this fault: Low water cutoff - Shop at Amazon
Parts that commonly fix the E302 code
- Water pressure sensorShop at Amazon
- Low water cutoffShop at Amazon